DIL switch settings TPI temperature control software
Thermostats using TPI (Time Proportional Integral) control algorithms will reduce the temperature
swing that normally occurs when using traditional bellows or thermally operated thermostats.
As a consequence, a TPI regulating thermostat will maintain the comfort level far more efficiently
than any traditional thermostat.
When used with a condensing boiler, the TPI thermostat will help to save energy as the control
algorithm allows the boiler to operate in condensing mode more
consistently compared to older types of thermostat.
DIL switch numbers 7 and 8 should be set as diagram opposite.
For Gas boilers set the TPI setting to 6 cycles per hour.
(Default setting)
For Oil boilers set the TPI setting to 3 cycles per hour.
For Electric heating set the TPI setting to 12 cycles per hour.
Switch positions for
different TPI settings.